Electrical installation guide

Aluminium Electrical Conduit

Aluminium electrical conduit is metal tubing, usually in 6063 alloy, that protects and routes electrical cables. It weighs about a third as much as steel conduit of the same size, does not rust, is non-magnetic and serves as a low-impedance earthing path. This guide covers rigid, EMT and flexible types, the standards behind them, size and weight tables, and where aluminium is and is not the right choice.

Aluminium conduit and tube used for electrical cable protection
Alloy
6063 (T1, T5), 6061
Types
Rigid · EMT · flexible
Standards
ANSI C80.5 · UL 6A · UL 797A
Weight
≈ ⅓ of steel conduit
Overview

What is aluminium electrical conduit?

Conduit is the protective raceway through which building and industrial cables are pulled. Metal conduit shields the conductors from impact, crushing, moisture and fire spread, and in most systems it also acts as the equipment earthing (grounding) conductor. Aluminium conduit does all of this at a fraction of the weight of steel.

Rigid aluminium conduit has been used in North American industrial and commercial installations for decades and is recognised alongside galvanised steel in the US National Electrical Code (NEC) and the Canadian Electrical Code. It is specified heavily in petrochemical plants, wastewater works, food plants, coastal buildings and data centres, and increasingly on rooftop solar and EV-charging projects, where corrosion resistance and easy handling matter.

Metline supplies aluminium tube and pipe in conduit alloys and dimensions, couplings stock, bar for fittings, and related extrusions, to conduit manufacturers, fabricators and project buyers worldwide. Where a project requires UL-listed or CSA-certified conduit, the listing is held by the conduit manufacturer and must appear on the product marking; tell us the requirement and we confirm what can be supplied for that project.

Conduit types

Rigid, EMT and flexible aluminium conduit

Rigid aluminium conduit (ARC / RMC)

Heavy-wall, threaded conduit with the same outside diameter and wall as steel rigid conduit. Covered by ANSI C80.5 and UL 6A and installed under NEC Article 344. Supplied in 10 ft (3.05 m) lengths with tapered NPT threads and one coupling. Used outdoors, in industrial plants and in hazardous (classified) locations with suitable fittings.

Aluminium EMT (electrical metallic tubing)

Thin-wall, unthreaded tubing joined with set-screw or compression fittings. Covered by UL 797A and installed under NEC Article 358. Easy to bend by hand bender and cut on site. Used indoors and in dry or damp locations where heavy mechanical protection is not needed.

Flexible aluminium conduit

Helically wound, interlocked aluminium strip that bends freely, used for short connections to motors, transformers and vibrating equipment. Flexible metal conduit (FMC) is listed to UL 1 and installed under NEC Article 348; liquid-tight versions add a PVC or similar jacket.

FeatureRigid aluminium conduitAluminium EMTFlexible aluminium conduit
WallHeavy (2.6 – 6.8 mm)Thin (1.1 – 2.1 mm)Interlocked strip
JointsThreaded couplingsSet-screw or compression fittingsScrew-in or clamp connectors
Mechanical protectionHighestModerateLow to moderate
Typical alloy6063-T1 (T5 in small sizes)6063Soft aluminium strip
Hazardous locationsYes, with listed fittingsGenerally noLimited, with listed fittings
Main standardsANSI C80.5, UL 6AUL 797AUL 1; IEC 61386-23
Material

Alloys used for aluminium conduit

Conduit is made almost entirely from 6063, the architectural extrusion alloy, because it extrudes into seamless tube with a smooth bore, threads cleanly and resists corrosion well. Low copper content is important: copper reduces the corrosion resistance of aluminium, so conduit makers keep it to a minimum, and some describe their conduit as "marine grade" for this reason.

Element6063 limits (wt %)Effect in conduit
Silicon (Si)0.20 – 0.60Forms Mg2Si with magnesium for strength
Magnesium (Mg)0.45 – 0.90Main strengthening element
Iron (Fe)≤ 0.35Impurity; kept low for surface quality
Copper (Cu)≤ 0.10Kept low for corrosion resistance
Manganese, chromium, zinc, titanium≤ 0.10 eachImpurities or trace additions
Aluminium (Al)RemainderAbout 97.5 – 99.4 %

Rigid conduit is commonly supplied in the T1 temper (cooled from extrusion and naturally aged), which gives enough strength for threading and field bending while keeping the metal ductile. Smaller sizes are sometimes supplied in T5. EMT uses 6063 in a temper that allows tight field bends without cracking. The interlocked strip of flexible conduit uses a soft, formable aluminium alloy. Where a customer needs extra strength, for example for long unsupported spans or custom raceways, 6061-T6 tube is an alternative.

Composition limits are the registered Aluminum Association values for 6063 (ASTM B221 / EN 573-3 EN AW-6063).

Dimensions

Rigid aluminium conduit and EMT size tables

Rigid aluminium conduit shares its outside diameter and wall thickness with rigid steel conduit, so the same fittings, threading dies and fill tables apply. Metric designators are the trade-size equivalents used in the NEC. Weights below are calculated from the nominal dimensions at 2.70 g/cm³ and exclude couplings.

Trade size (in)Metric designatorOutside diameter (mm)Nominal wall (mm)Weight (kg/m)
½1621.32.640.42
¾2126.72.720.55
12733.43.200.82
1¼3542.23.381.11
1½4148.33.511.33
25360.33.711.78
2½6373.04.902.83
37888.95.213.70
3½91101.65.464.45
4103114.35.725.26
5129141.36.227.13
6155168.36.769.26

Outside diameters and walls follow the nominal values used for rigid metal conduit under ANSI C80.5; the standard sets the tolerances. Manufacturers’ published weights per 100 ft are slightly higher because they include the coupling.

Aluminium EMT uses the same outside diameters and nominal walls as steel EMT, so standard EMT connectors, couplings and benders fit. The thin wall keeps weight very low:

Trade size (in)Outside diameter (mm)Nominal wall (mm)Weight (kg/m)
½17.91.070.15
¾23.41.240.23
129.51.450.35
1¼38.41.650.51
1½44.21.650.60
255.81.650.76
2½73.01.831.10
388.91.831.35
3½101.62.111.78
4114.32.112.01

Typical supply range

Rigid conduit
Trade sizes ½ – 6 in, 10 ft (3.05 m) lengths, NPT threaded both ends with one coupling, colour-coded thread protectors
EMT
Trade sizes ½ – 4 in, 10 ft (3.05 m) lengths, plain ends
Metric conduit tube
Plain-end aluminium tube to IEC 61386 or project dimensions, 16 – 63 mm and larger
Finish
Mill finish standard; anodised or powder coated for exposed architectural runs
Processing
Cut lengths, threading, factory bends and elbows to drawing on request
Standards

Standards and codes for aluminium conduit

Standard / codeScope
ANSI C80.5Electrical rigid metal conduit, aluminium: dimensions, threads, coupling, bending and finish requirements
UL 6AElectrical rigid metal conduit, aluminium, red brass and stainless steel: safety listing requirements
UL 797AElectrical metallic tubing, aluminium and stainless steel
UL 1Flexible metal conduit, including aluminium
NEC Articles 344, 358, 348Installation rules for rigid metal conduit, EMT and flexible metal conduit (US)
NEC 300.6Corrosion protection; aluminium conduit in concrete or in contact with soil needs supplementary protection
CSA C22.2 No. 45.2Rigid metal conduit in aluminium and other non-ferrous metals (Canada)
IEC 61386-1, -21, -23Conduit systems for cable management: general, rigid and flexible (international / EN 61386)
ASME B1.20.1Tapered pipe threads (NPT) used on rigid conduit
ASTM B221 / B241Extruded tube and seamless pipe material specifications for the aluminium itself

A note on accuracy: some online sources list IEC 61386-24 for flexible conduit (part 24 covers conduit buried underground; flexible conduit is part 23) and ASTM B308 as a salt-spray standard (B308 is a specification for 6061-T6 structural profiles). Check the scope of any standard quoted in a tender before relying on it.

Comparison

Aluminium conduit compared with galvanised steel and PVC

PropertyRigid aluminiumGalvanised rigid steelPVC conduit
Weight (2 in trade size)About 1.8 kg/mAbout 5.4 kg/mVery light
Corrosion in industrial and coastal airExcellent; no coating to wear throughGood until zinc is consumedExcellent
Corrosion in concrete and soilNeeds supplementary protectionOften needs extra coatingExcellent
MagneticNoYesNo
Acts as earthing conductorYes, low impedanceYesNo; separate earth wire needed
Mechanical protectionHighHighestLow to moderate
Fire behaviourNon-combustibleNon-combustibleCombustible; smoke and fumes
Thermal expansion23 µm/m·°C12 µm/m·°CAbout 50 – 70 µm/m·°C

In practice aluminium is the best choice for exposed runs in corrosive atmospheres, high-level and roof installations where weight and handling matter, and installations near sensitive equipment. Steel remains preferable where the conduit will be cast into concrete or buried without extra protection, or where the highest crush resistance is required. PVC dominates underground ducts and very wet locations but cannot serve as an earth path and needs expansion fittings on long runs.

Installation

Installation guidance for aluminium conduit

  • Cutting and threading: use sharp, fine-tooth blades and threading dies with cutting oil suited to aluminium; ream every cut end to remove burrs that could damage cable insulation
  • Bending: aluminium bends with standard benders but springs back slightly more than steel; use the bender maker’s aluminium settings and do not exceed the minimum radius for the trade size
  • Thread compound: apply an electrically conductive, anti-seize compound to threads to keep the earthing path reliable and prevent galling
  • Dissimilar metals: use aluminium, stainless steel or suitably coated fittings and straps; isolate aluminium from copper and bare steel in wet locations
  • Concrete and soil: wrap, coat or sleeve aluminium conduit where it enters concrete or the ground, as NEC 300.6 requires; chlorides and alkalis in fresh concrete attack aluminium
  • Expansion: on long straight outdoor runs, allow for expansion of about 2.3 mm per 10 m for each 10 °C change, using expansion fittings where needed
  • Supports: follow the support spacing in the electrical code for the trade size; aluminium conduit is listed with the same spacing rules as steel rigid conduit
Applications

Where aluminium conduit is used

ApplicationTypical typeWhy aluminium
Chemical, petrochemical and refinery plantsRigidResists industrial atmospheres; light for rack and pipe-bridge installation
Wastewater and water treatmentRigidResists humid, sulphide-bearing air better than galvanised steel in many cases
Food and beverage plantsRigid, EMTNo rust flakes; tolerates frequent wash-down with suitable fittings
Coastal and marine buildingsRigidWithstands salt-laden air without coating maintenance
Data centres, hospitals, labsEMT, rigidNon-magnetic, low voltage drop, fast to install overhead
Rooftop solar and EV chargingRigid, EMTLight on roofs, UV-stable, corrosion resistant outdoors
Motors, pumps and machinesFlexibleAbsorbs vibration and movement at equipment connections
Hazardous locationsRigid with listed fittingsAccepted for classified areas under the electrical code
Ordering

How to order aluminium conduit tube from Metline

  1. SpecifyConduit type, trade size or OD × wall, alloy and temper, length, ends (plain or threaded) and the governing standard.
  2. Confirm listing needsTell us if the installation requires UL, CSA or IEC-certified product so we can confirm what can be supplied with the right marking and documents.
  3. QuoteWe confirm availability, tolerances, packing and delivery terms (EXW, FOB, CIF or DAP).
  4. InspectDimensions, straightness and surface checked; mill test certificate to EN 10204 3.1 issued for the lot.
  5. ShipBundled with end caps or in wooden cases for export, by sea or air.
Sources

References and standards

  1. ANSI C80.5 – American National Standard for Electrical Rigid Metal Conduit, Aluminum
  2. UL 6A – Electrical Rigid Metal Conduit: Aluminum, Red Brass and Stainless Steel
  3. UL 797A – Electrical Metallic Tubing: Aluminum and Stainless Steel
  4. NFPA 70 – National Electrical Code, Articles 300, 344, 348 and 358
  5. IEC 61386 series – Conduit systems for cable management
  6. The Aluminum Association – International Alloy Designations and Chemical Composition Limits
FAQ

Aluminium (aluminum) electrical conduit: frequently asked questions

Is aluminium conduit allowed by the electrical code?

Yes. The US National Electrical Code covers aluminium rigid metal conduit under Article 344 and aluminium EMT under Article 358, and the Canadian Electrical Code recognises it too. The product must be listed for the purpose, and aluminium in concrete or in contact with soil needs supplementary corrosion protection.

How much lighter is aluminum conduit than steel?

About one third the weight for the same trade size. A 2 in rigid aluminium conduit weighs roughly 1.8 kg per metre, compared with about 5.4 kg per metre for galvanised rigid steel.

Can aluminium conduit be used as the earthing conductor?

Yes. Rigid aluminium conduit and aluminium EMT are recognised as equipment grounding (earthing) conductors when installed with listed fittings. Aluminium’s good conductivity gives a low-impedance fault path; use conductive thread compound to keep joints reliable.

Can aluminium conduit be buried or cast in concrete?

Only with supplementary corrosion protection such as a factory coating, wrapping or sleeving, as required by NEC 300.6. Fresh concrete is alkaline and may contain chlorides, both of which attack bare aluminium.

Which alloy is used for aluminium conduit?

6063 is standard, typically in the T1 temper for rigid conduit, with low copper content for corrosion resistance. 6061-T6 tube can be used where extra strength is needed for custom raceways.

Does aluminium conduit reduce voltage drop?

Compared with steel conduit, yes. Because aluminium is non-magnetic, AC circuits in aluminium conduit have lower reactance and therefore lower voltage drop and less inductive heating of the raceway, which helps on long feeders.

Need aluminium conduit tube?

Send the type, size, length, quantity and certification needs. We will confirm availability and a delivered price for your project worldwide.