1350 / 1370
The electrical conductor grade, 99.5 % aluminium or better, with controlled trace elements for high conductivity. Best choice for flat plates that are only lightly formed.
A laminated busbar is a stack of thin, flat conductor plates separated by insulating film and bonded into one rigid part, so that the positive and negative current paths sit a fraction of a millimetre apart. That geometry cancels most of the magnetic field, cuts stray inductance to a few nanohenries and keeps switching overvoltage under control in inverters, converters and battery systems. This guide explains how the design works and how to specify the aluminium conductor layers, which Metline supplies as cut-to-drawing sheet, plate and strip.

A laminated busbar replaces a bundle of cables or separate bars with a single engineered sandwich: conductor, insulation, conductor, insulation, sealed at the edges and fitted with tabs, holes or press-in terminals where devices and capacitors connect.
The reason for building it this way is inductance. Every conductor loop stores magnetic energy, and when a power transistor (IGBT, SiC or GaN MOSFET) switches off a large current in tens of nanoseconds, that stored energy appears as a voltage spike: V = L × di/dt. Switching 1,000 A in 100 ns gives di/dt of 10 kA/µs; with 20 nH of loop inductance the spike is about 200 V, with 5 nH it falls to about 50 V. A smaller spike lets the designer use devices closer to their voltage rating, run faster switching edges and reduce snubber components.
Putting the DC+ and DC− plates face to face, separated only by insulation film, makes currents flow in opposite directions over a wide area. Their magnetic fields largely cancel, which is why laminated busbars are standard in traction inverters, wind and solar converters, industrial drives, UPS systems, rail propulsion and battery energy storage.
Most designs follow the same build-up, whatever the conductor metal. The number of layers depends on the circuit: a two-level DC link needs two conductors, a three-level converter usually needs three or four, and multi-phase assemblies can exceed six.
| Layer | Typical material | Function and design notes |
|---|---|---|
| Conductor plates | Aluminium 1350, 1060, 1070 or 6101; copper C11000 or C10200 | Carry current. Thickness usually 0.5 – 3 mm; width set by current density and temperature rise. |
| Inter-layer insulation | Polyester (PET) film, polyimide (PI) film, aramid paper, epoxy-glass laminate | Isolates potentials. Film thickness of roughly 0.1 – 0.5 mm per layer, chosen for voltage, partial discharge and temperature. |
| Adhesive system | Thermoset or hot-melt adhesive coated on the film | Bonds the stack under heat and pressure without voids, which would cause partial discharge. |
| Edge treatment | Film overhang, edge fill, epoxy powder coating or encapsulation | Provides creepage distance around the plate edges and keeps out moisture and dust. |
| Terminals | Tabs formed from the plate, press-in nuts or studs, bushings | Connect to modules, capacitors and cables; usually plated for stable contact resistance. |
| Outer insulation | PET, PI or powder coat | Protects personnel and adjacent parts; often colour-coded by potential. |
Inductance of two parallel plates is roughly proportional to the plate separation divided by the plate width (L ≈ μ0 × length × separation / width). That simple relationship explains the design rules: keep the insulation as thin as voltage and partial-discharge limits allow, make the plates wide, and keep the DC+ and DC− plates overlapping all the way to the device terminals. As an example, a 300 mm long, 100 mm wide plate pair separated by 0.25 mm has a calculated loop inductance of about 1 nH before terminal and via effects are added; real assemblies land higher because of holes, cut-outs and terminal geometry.
Copper has been the default because it packs the most conductivity into the smallest volume. Aluminium has become common in battery packs, energy storage systems and EV drive units because it removes about half the conductor mass for the same resistance, costs less per ampere and is easy to cut, punch and form.
| Property | Aluminium 1350 | Aluminium 6101-T61 | Copper C11000 |
|---|---|---|---|
| Electrical conductivity (IACS) | 61 % minimum (bus bar) | 57 % minimum | 100 % minimum (annealed) |
| Density | 2.70 g/cm³ | 2.70 g/cm³ | 8.89 – 8.94 g/cm³ |
| Cross-section for equal resistance | About 1.6 × copper | About 1.75 × copper | 1.0 × |
| Mass for equal resistance | About 0.5 × copper | About 0.53 × copper | 1.0 × |
| Strength | Low; easy to form | Medium; stiffer plates and tabs | Medium |
| Contact surface | Oxide film; needs plating or prepared joints | Oxide film; needs plating or prepared joints | Easy to plate and bolt |
Conductivity minimums: 1350 bus conductor per ASTM B236; 6101 tempers per ASTM B317 (T6 55 %, T61 57 %, T63 56 %, T64 59.5 %, T65 56.5 % IACS). Copper per ASTM B187 / IACS definition. Mass ratios are calculated from conductivity and density.
The practical consequence is that an aluminium layer is thicker or wider than the copper layer it replaces. Because loop inductance depends on separation and width rather than conductor thickness, a wider aluminium plate can actually help inductance; a thicker one increases the overall stack height slightly. Where space is very tight and currents are high, copper still wins; where weight and cost dominate, as in most battery and storage systems, aluminium is usually the better engineering choice.
The electrical conductor grade, 99.5 % aluminium or better, with controlled trace elements for high conductivity. Best choice for flat plates that are only lightly formed.
Commercially pure grades with conductivity close to 1350, widely available as sheet and coil. Common for punched and bent laminated plates.
Heat-treatable Al-Mg-Si conductor alloy that is much stronger than 1xxx grades while keeping 55 – 59.5 % IACS. Used where tabs or long spans must stay rigid.
Structural extrusion grades sometimes used for thick bus sections; conductivity is lower than 6101, so check the temper value on the certificate.
An aluminium core with a metallurgically bonded copper skin, giving copper contact surfaces at reduced weight. See our copper-clad aluminium bus bar guide.
Pairs well where highest current density is needed. Metline supplies the aluminium options only; the copper column above is for comparison.
Insulation selection balances three things: dielectric strength (and partial-discharge inception voltage), operating temperature, and thickness, because every extra micrometre raises inductance. Voids, wrinkles and sharp plate edges are where failures start, so the lamination process and edge design matter as much as the film itself.
| Material | Typical use | Strengths | Limits |
|---|---|---|---|
| Polyester (PET) film | Most low- and medium-voltage laminated busbars | Low cost, good dielectric strength, easy to laminate | Lower temperature ceiling than PI |
| Polyimide (PI) film | High-temperature zones near power modules, aerospace | High temperature rating, thin for its strength | Higher cost; absorbs some moisture |
| Aramid paper | Edge wraps, high-temperature insulation | Thermal endurance, conformability | Thicker than films for the same voltage |
| Epoxy-glass laminate (FR4 / G10 type) | Rigid spacers and thick insulation between sub-assemblies | Mechanical stiffness, good machinability | Thick; raises inductance |
| Epoxy powder coating | Edge sealing and full encapsulation | Seals edges, adds creepage | Coating thickness must be controlled |
A widely quoted design rule in the industry is about 1 mm of rigid insulation per kilovolt between sub-assemblies, but the governing requirement is the partial-discharge limit: the electric field (voltage divided by distance) at the worst point must stay below the level at which discharges start. Designs for altitude, such as aircraft or high-altitude solar sites, need extra margin because partial-discharge inception voltage falls as air pressure drops. Creepage and clearance at exposed edges follow the insulation-coordination rules in IEC 60664-1 for the relevant pollution degree and overvoltage category.
Laminated busbars are tested as electrical insulation systems and as conductors. A typical production and qualification programme looks like this:
| Test | What it checks | Common reference |
|---|---|---|
| Dielectric withstand (hi-pot) | Insulation does not break down at test voltage, AC or DC | Customer specification; IEC 61439 / IEC 61800-5-1 test levels for the end equipment |
| Partial discharge | Discharge magnitude (pC) at a defined voltage, and inception/extinction voltage | IEC 60270 measurement method |
| Insulation resistance | Leakage resistance between layers, typically at 500 – 1,000 V DC | Customer specification |
| Stray inductance | Loop inductance at the device terminals | Double-pulse test or impedance analyser |
| Temperature rise | Conductor heating at rated current | IEC 61439-1 approach for assemblies |
| Flammability of insulants | Burning behaviour of films and coatings | UL 94 ratings of the insulation materials |
| Conductor material | Chemistry, temper and electrical conductivity of the aluminium | ASTM B236, ASTM B317, EN 14121; EN 10204 3.1 certificate |
For the aluminium layers, the most useful document is the mill test certificate. It should show the alloy and temper, chemical analysis and, for conductor grades, the measured electrical conductivity or resistivity. Ask for conductivity to be reported in % IACS or MS/m so it can be compared directly with your thermal model.
Metline supplies the aluminium that goes into the conductor layers; the lamination, insulation, plating and final electrical testing are carried out by the busbar maker. Typical requests we handle:
Confirm plating, flatness and burr requirements on your drawing so the stock can be prepared for your lamination process.
Yes. Aluminium conductor layers (1350, 1060 or 6101) are widely used in battery packs, energy storage and inverters. They need roughly 1.6 times the cross-section of copper for the same resistance but weigh about half as much. Contact areas are normally plated, and joints are designed for aluminium.
Well-designed laminated busbars typically reach single-digit to a few tens of nanohenries at the device terminals, depending on plate width, insulation thickness and terminal layout. Cable or separated-bar connections are usually far higher.
1350 or 1060/1070 for flat or lightly formed plates where conductivity is the priority; 6101 in T6, T61 or T64 where plates or tabs must be stiffer. Avoid general structural alloys unless strength governs, because their conductivity is lower.
Polyester (PET) film is the most common; polyimide (PI) is used for higher temperatures; aramid paper, epoxy-glass laminate and epoxy powder coating are used for edges, spacers and encapsulation.
Typical tests are dielectric withstand (hi-pot), partial discharge to the IEC 60270 method, insulation resistance, stray inductance by double-pulse test and temperature rise. The aluminium layers are checked against their mill certificate for alloy, temper and conductivity.
No. Metline supplies the aluminium conductor stock (sheet, plate, strip, flat bar and copper-clad aluminium), cut or machined to your flat pattern with mill certificates, to busbar makers and OEMs worldwide. Lamination and insulation are done by the assembler.
Send the grade, temper, thickness, flat pattern and quantity. We reply with availability, processing options, certification and delivered pricing.