Copper Clad Aluminium (CCA)

Copper clad aluminium is a bimetallic conductor in which a layer of copper is metallurgically bonded to an aluminium core, so the material has a copper surface and an aluminium body. It is made as wire, flat bar (busbar), plate, strip and foil, typically with 10 – 35 % copper by volume. This guide explains how CCA is produced, what it can and cannot do compared with solid copper and solid aluminium, and how to choose the right form and copper ratio.

Electrical conductors and busbars used in power distribution equipment
Photo: Kreuzschnabel, Wikimedia Commons, CC BY-SA 3.0
Structure
Copper skin, aluminium core
Copper ratio
10 – 35 % by volume
Forms
Wire, bar, plate, strip, foil
Standards
ASTM B566 · ASTM B1005
Overview

What copper clad aluminium is

CCA is not plated aluminium. The copper layer is joined to the aluminium over the whole interface by pressure and heat, so the two metals form a solid-state metallurgical bond and are worked together, drawn, rolled, bent and punched, as a single material. A properly bonded CCA product does not delaminate when bent, twisted or cut.

The idea is to put each metal where it does most good. Copper on the outside gives a surface that is easy to solder, crimp and bolt, resists oxidation, and makes reliable contact with existing copper terminals. Aluminium in the core supplies most of the cross-section at about 30 % of the density of copper and a fraction of its cost per kilogram.

The copper fraction is expressed by volume (or by area of the cross-section), and it stays constant as the material is drawn or rolled to smaller sizes. Wire normally carries 10 % or 15 % copper; busbar and plate typically 20 – 35 %; strip and foil cover a wide range depending on whether one or both faces are clad.

Manufacturing

How copper clad aluminium is produced

ProcessHow it worksTypical products
Cladding and welding (tape cladding)Copper tape is formed around a clean aluminium rod, seam-welded, then drawn so the layers bond under pressureCCA wire for coaxial cable, braid, winding wire
Continuous casting / cast-claddingMolten aluminium is cast into a pre-formed copper tube, then the composite is rolled or drawnFlat bar, rod and busbar
Hydrostatic extrusion and co-extrusionA copper-sleeved aluminium billet is extruded under fluid pressure so both metals flow togetherRod, bar and profiled sections
Roll bonding (cold or hot)Wire-brushed copper and aluminium strips are stacked and rolled with heavy reduction, then annealed to strengthen the bondPlate, sheet, strip, foil; one-side, two-side and inlay
Explosion bondingAn explosive charge drives the copper plate onto the aluminium at high velocityThick plate, transition blocks, electrolytic cell connectors

Whatever the route, the critical factor is the interface. Copper and aluminium form brittle intermetallic compounds (Al2Cu, AlCu, Al4Cu9) when they are held at high temperature. A thin intermetallic layer is tolerable; a thick one makes the bond brittle and raises interface resistance. Producers therefore control annealing temperature and time carefully, and users should avoid exposing CCA to prolonged temperatures above roughly 200 – 250 °C, and to any heating approaching 400 °C, which published studies associate with rapid intermetallic growth and debonding.

Data

How copper ratio affects density, conductivity and weight

Because the two metals act in parallel, density and DC conductivity follow a simple rule of mixtures. The table shows calculated values for common copper ratios and what they mean in practice.

Copper by volumeDensity (g/cm³)Weight vs copper, same sizeCalculated conductivityArea needed vs copper, same resistanceWeight vs copper, same resistance
10 %3.3237 %≈ 65 % IACS1.54 ×58 %
15 %3.6341 %≈ 67 % IACS1.50 ×61 %
20 %3.9444 %≈ 69 % IACS1.45 ×64 %
25 %4.2548 %≈ 71 % IACS1.41 ×68 %
30 %4.5651 %≈ 73 % IACS1.38 ×71 %
35 %4.8755 %≈ 75 % IACS1.34 ×73 %

Rule-of-mixtures values calculated from copper (8.89 g/cm³, 100 % IACS) and an aluminium core of 2.70 g/cm³ and 61 % IACS. They are upper estimates: hard tempers and 1060/1070 cores conduct slightly less. Guaranteed values are the minimums in the governing standard and on the test certificate.

Read the last column carefully. For DC or low-frequency AC, a CCA conductor of equal resistance weighs about 60 – 75 % of the copper it replaces, while a solid aluminium conductor of equal resistance weighs only about 50 %. CCA is therefore not the lightest option; its value is that it combines most of aluminium's savings with a copper surface. At radio frequencies, where current crowds into the outer skin, a CCA conductor with enough copper thickness behaves almost exactly like solid copper, which is why CCA dominates coaxial cable inner conductors.

Products

Forms of copper clad aluminium

Comparison

CCA compared with solid copper and solid aluminium

CriterionSolid copperCopper clad aluminiumSolid aluminium
DC conductivity100 % IACSAbout 64 – 75 % IACSAbout 61 % IACS (1350)
Weight for equal resistance100 %About 60 – 75 %About 50 %
Contact surfaceCopperCopperAluminium; needs plating or compound
Termination with copper lugsDirectDirectBimetal lugs or transition needed
Strength and fatigueHighestBetween the two; core dominatesLowest (1350); alloys like 6101 better
Heat toleranceHighLimited by interface (avoid long exposure above about 200 – 250 °C)Moderate
RecyclingSimple, high valueNeeds separation of metalsSimple
Material costHighestIntermediateLowest

The right answer depends on what limits your design. If weight is the limit and the joints can be engineered for aluminium, solid aluminium is lighter and cheaper still. If the conductor must terminate on copper hardware without special parts, or must be soldered, CCA earns its place. If space is the limit, copper remains the most compact choice.

Honest limits

Where CCA is not the right choice

  • Building wiring and Ethernet cable. Many building codes and the TIA/ISO structured-cabling standards require solid copper conductors. CCA "network cable" sold as Cat 5e or Cat 6 does not meet those standards and runs hotter in Power over Ethernet service.
  • High-temperature terminations. Joints that run hot for long periods can grow intermetallic compounds at the copper-aluminium interface.
  • Severe flexing. Repeated bending fatigues the softer aluminium core sooner than solid copper.
  • Cut ends in damp environments. The exposed aluminium core at a cut face is a galvanic couple with the copper skin; seal ends or keep them dry.
  • Where the specification says copper. Substituting CCA without approval is a common source of disputes and failed inspections; always declare the material.
Standards

Standards for copper clad aluminium

StandardScope
ASTM B566 / B566MCopper-clad aluminium wire: 10 % and 15 % copper classes, annealed and hard
ASTM B1005Copper-clad aluminium bar for electrical purposes (bus bar): 20, 25 and 30 % copper, annealed (A) and hard (H) classes
ASTM B209 / EN 485Aluminium sheet and plate (core material reference)
ASTM B152 / EN 1652Copper sheet, strip and plate (cladding material reference)
IEC 61439Switchgear assemblies, when CCA busbar is used inside them

For roll-bonded plate and strip there is no single international product standard, so orders are normally placed to an agreed specification covering layer ratio, total thickness tolerance, temper, bond strength (peel or shear test), bend test and conductivity. Ask for those values on the test certificate.

Ordering

How to specify copper clad aluminium

  1. Form and dimensionsWire diameter, or bar/plate/strip thickness, width and length or coil size.
  2. Structure and copper ratioCopper by volume (for example 15 % wire, 25 % bar) and, for plate and strip, one-side, two-side or inlay layout with layer thicknesses.
  3. Core and copper gradesUsually 1060 or 1070 aluminium core with C11000 or C10200 copper; state any alternatives.
  4. Temper and propertiesAnnealed or hard, minimum tensile strength, elongation and conductivity.
  5. Tests and documentsBond test, bend test, resistivity, dimensions; EN 10204 3.1 certificate and packing list.
  6. DeliveryPacking (reels, coils, wooden cases), quantity, destination and Incoterm (EXW, FOB, CIF, DAP).
Sources

References and standards

  1. ASTM B566/B566M – Standard Specification for Copper-Clad Aluminum Wire
  2. ASTM B1005 – Standard Specification for Copper-Clad Aluminum Bar for Electrical Purposes (Bus Bar)
  3. ASTM B209 – Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
  4. The Aluminum Association – Aluminum Electrical Conductor Handbook
  5. ASM Handbook, Vol. 2 – Properties and Selection: Nonferrous Alloys and Special-Purpose Materials
FAQ

Copper clad aluminium (aluminum): frequently asked questions

What is copper clad aluminum?

Copper clad aluminum (CCA) is an aluminium core with a copper layer bonded to it metallurgically, not plated. It is produced as wire, busbar, plate, strip and foil, usually with 10 – 35 % copper by volume.

Is CCA as good as copper?

Not for DC resistance: CCA conducts roughly 64 – 75 % as well as copper, so a larger cross-section is needed for the same resistance. Its surface behaves like copper for soldering, crimping and bolting, and at radio frequencies it performs almost like solid copper.

How much lighter is CCA than copper?

Size for size, CCA with 10 – 35 % copper weighs about 37 – 55 % as much as copper. For the same resistance the saving is smaller, about 25 – 40 %, because the CCA section has to be larger.

Can CCA be soldered and crimped?

Yes. The copper surface accepts normal solders and crimp terminals. Avoid overheating during soldering and protect cut ends from moisture, where the aluminium core is exposed.

Is CCA cable allowed for building wiring?

Generally not. Most electrical codes and structured-cabling standards require solid copper (or approved aluminium) conductors for fixed building wiring and Ethernet cabling. CCA is used in coaxial cable, winding wire, busbar and specialised assemblies where it is specified and approved.

What copper ratio should I choose?

Wire is normally 10 % or 15 % copper. Busbar is commonly 20 – 30 %. Higher copper content raises conductivity and joint robustness, while lower content saves weight and cost. Match the ratio to the governing standard and your termination method.