Menu
Electrical conductor guide

6063-T6 Aluminium Tubular Bus Pipe for Substations and Switchyards

6063-T6 tubular bus pipe is seamless aluminium pipe used as a rigid conductor in substations, switchyards and generator connections. It combines about 53 % IACS conductivity with enough strength to span between insulators, and its round shape keeps corona low at high voltage. This guide covers sizes with calculated weights and resistance, the standards that apply, how 6063 compares with 6101 and 6061, and the design points engineers check.

Aluminium tubular bus conductors in an outdoor electrical substation
Alloy and temper
6063-T6 (seamless)
Conductivity
About 53 % IACS
Usual sizes
NPS 1 – 8, Schedule 40 and 80
Standard
ASTM B241 · IEEE 605 design
Overview

What is aluminium tubular bus pipe?

In an air-insulated substation, rigid bus connects transformers, breakers, disconnectors and line bays. Rigid tubular bus replaces stranded conductors where spans are short to medium, where clearances must be held precisely, and where low maintenance and a tidy layout matter.

A tube is efficient for this job. Alternating current crowds towards the outer surface of a conductor (skin effect), so the metal at the centre of a solid bar carries little current; a tube puts all its metal where it works. The round section also has the same stiffness in every direction, and a smooth large diameter lowers the surface voltage gradient that causes corona discharge, radio interference and audible noise at higher voltages.

6063-T6 seamless pipe in ANSI schedule 40 dimensions is the most widely used bus tube in North America and many export markets. It offers a practical balance: conductivity of about 53 % IACS, a guaranteed yield of around 170 MPa to carry its own weight, ice and short-circuit forces between supports, and good weldability to aluminium bus fittings.

Alloy choice

6063-T6 compared with 6101 and 6061 bus conductors

Alloy and temperConductivity (typical)StrengthSpecificationWhen used
6063-T6About 53 % IACSYield min about 172 MPa (25 ksi)ASTM B241 (seamless pipe)General outdoor substation bus; the usual default
6101-T6 / T61 / T63 / T64About 55 – 59 % IACS, by temperLower to similar, by temperASTM B317 (bus conductor)Where higher conductivity outweighs strength, such as generator and indoor bus
6061-T6About 43 % IACSYield min about 241 MPa (35 ksi)ASTM B241Long spans or high short-circuit forces where strength governs
1350 / 1060 tubeAbout 61 – 62 % IACSLowConductor-grade specificationsShort, well-supported runs and flexible connections

ASTM B317 is the specification written specifically for extruded aluminium bus conductors, and it covers 6101. 6063-T6 bus pipe is normally supplied as seamless pipe to ASTM B241 with conductivity confirmed by test. Read our 6101 bus pipe guide and 6061 bus pipe guide for those options.

Size tables

6063-T6 bus pipe, Schedule 40 sizes

Dimensions follow ANSI/ASME B36.10 pipe schedules. Area and weight are calculated from nominal OD and wall with a density of 2.70 g/cm³; DC resistance is calculated at 20 °C for 53 % IACS. Use these values for early design; final ratings should come from the conductor manufacturer's data and a calculation to IEEE 605 or your national code.

NPSOD (in / mm)Wall (in / mm)Area (in²)Weight (lb/ft)Weight (kg/m)DC resistance at 20 °C (µΩ/m)
11.315 / 33.40.133 / 3.380.4940.5780.86102.1
1¼1.660 / 42.20.140 / 3.560.6690.7821.1675.4
1½1.900 / 48.30.145 / 3.680.7990.9351.3963.1
22.375 / 60.30.154 / 3.911.0751.2571.8746.9
2½2.875 / 73.00.203 / 5.161.7041.9942.9729.6
33.500 / 88.90.216 / 5.492.2282.6073.8822.6
3½4.000 / 101.60.226 / 5.742.6803.1354.6718.8
44.500 / 114.30.237 / 6.023.1743.7145.5315.9
55.563 / 141.30.258 / 6.554.3005.0317.4911.7
66.625 / 168.30.280 / 7.115.5816.5309.729.0
88.625 / 219.10.322 / 8.188.3999.82714.636.0
Size tables

6063-T6 bus pipe, Schedule 80 sizes

Schedule 80 has thicker walls for the same outside diameter. It carries more current and resists higher short-circuit forces, at the cost of extra weight on the insulators.

NPSOD (in / mm)Wall (in / mm)Area (in²)Weight (lb/ft)Weight (kg/m)DC resistance at 20 °C (µΩ/m)
11.315 / 33.40.179 / 4.550.6390.7471.1178.9
1¼1.660 / 42.20.191 / 4.850.8811.0311.5457.2
1½1.900 / 48.30.200 / 5.081.0681.2501.8647.2
22.375 / 60.30.218 / 5.541.4771.7282.5734.1
2½2.875 / 73.00.276 / 7.012.2542.6373.9322.4
33.500 / 88.90.300 / 7.623.0163.5295.2516.7
3½4.000 / 101.60.318 / 8.083.6784.3046.4113.7
44.500 / 114.30.337 / 8.564.4075.1577.6811.4
55.563 / 141.30.375 / 9.526.1127.15110.658.2
66.625 / 168.30.432 / 10.978.4059.83414.646.0
88.625 / 219.10.500 / 12.7012.76314.93222.234.0

Metric bus tubes are also widely used, particularly for 66 – 500 kV substations designed to IEC practice, with outside diameters from about 60 mm to 250 mm and above and walls of about 4 – 15 mm. Send the OD and wall thickness and we will confirm availability.

Material data

Composition, mechanical and electrical properties

ElementMin %Max %
Silicon (Si)0.200.60
Iron (Fe)—0.35
Copper (Cu)—0.10
Manganese (Mn)—0.10
Magnesium (Mg)0.450.90
Chromium (Cr)—0.10
Zinc (Zn)—0.10
Titanium (Ti)—0.10
Others, each / total—0.05 / 0.15
Aluminium (Al)Remainder
Property6063-T6 valueNote
Tensile strength207 MPa (30 ksi) min; about 241 MPa typicalASTM B241 / B221 minimum
Yield strength (0.2 %)172 MPa (25 ksi) min; about 214 MPa typical
Elongation8 – 12 %Depends on wall thickness
Electrical conductivityAbout 53 % IACSVolume conductivity at 20 °C
ResistivityAbout 0.0325 Ω·mm²/mAt 20 °C
Temperature coefficient of resistanceAbout 0.0035 per °CApproximate, at 20 °C
Density2.70 g/cm³
Thermal expansion23.4 µm/m·°CAbout 23 mm per 10 m for a 100 °C change
Modulus of elasticity68.9 GPaUsed for deflection and vibration calculations

The old figure of 2.75 g/cm³ sometimes quoted for 6063 density is incorrect; the registered value is about 2.69 – 2.70 g/cm³.

Engineering

What engineers check when designing tubular bus

Ampacity

Current rating depends on allowable temperature rise, ambient temperature, wind, solar gain and surface emissivity. A weathered or painted surface radiates heat better than bright metal. Ratings are calculated to IEEE 605 or the national equivalent.

Span and deflection

The bus must carry its own weight, ice and wind between supports within a deflection limit, often expressed as a fraction of the span. A larger diameter is the most effective way to increase stiffness.

Short-circuit forces

Fault currents create large electromagnetic forces between phases. The tube, insulators and fittings must withstand them; Schedule 80 or 6061-T6 is used where forces are high.

Aeolian vibration

Wind can set long tubes vibrating. Damping conductors (stranded cable inside the tube) or proprietary dampers are installed on longer spans.

Thermal expansion

Aluminium expands about twice as much as steel. Expansion fittings or sliding supports are needed so the bus does not load insulators as temperature changes.

Corona

At higher voltages the surface gradient must stay below the corona onset level. Larger diameters, smooth surfaces and corona caps or bells at tube ends are used.

Installation

Welding, connections and surface finishes

  • Welding: fittings are commonly welded with ER4043 filler by MIG or TIG; welding softens the tube locally, so welds are placed near supports where bending stress is low
  • Bolted connections: clean contact surfaces, use contact compound and spring washers, and tighten to the fitting manufacturer's torque
  • Connecting to copper: use bimetallic transition pieces or tin-plated contact areas to avoid galvanic corrosion
  • Bending: large-radius bends can be made with mandrel tooling; most layouts use straight runs with angle fittings
  • Finishes: usually mill finish; tin or silver plating on contact areas, and paint or a dark finish where higher emissivity is wanted
  • Handling: protect pipe ends and surfaces from dents and scratches, which can raise local electric stress at high voltage
Applications

Where 6063 bus pipe is used

  • Outdoor air-insulated substations and switchyards: main bus, bay connections and equipment jumpers
  • Generator and transformer connections at power stations
  • Industrial plant distribution, such as smelters, steelworks and chemical plants
  • Renewable energy collector substations for wind and solar farms
  • Rail traction substations and high-current DC systems

A typical example: an outdoor 132 kV substation uses 4 in Schedule 40 6063-T6 tube for its main bus, supported on post insulators, with welded or bolted fittings, damping cable on the longer spans and expansion fittings at regular intervals.

Ordering

How to order 6063-T6 bus pipe

  1. SpecifyNPS and schedule or OD × wall, length per piece, quantity, specification (ASTM B241 or other) and any conductivity requirement.
  2. QuoteWe confirm availability, tolerances, testing and delivery terms (EXW, FOB, CIF or DAP).
  3. ProcessCutting to length, end preparation and plating of contact areas on request.
  4. DocumentEN 10204 3.1 certificate with chemistry, tensile results and conductivity where specified.
  5. ShipEnd caps and protective wrapping, packed in wooden cases or crates for export.
Sources

References and standards

  1. ASTM B241/B241M – Aluminum and aluminum-alloy seamless pipe and seamless extruded tube
  2. ASTM B317/B317M – Aluminum-alloy extruded bar, rod, tube, pipe and profiles for electrical purposes (bus conductor)
  3. IEEE Std 605 – Guide for Bus Design in Air Insulated Substations
  4. ASME B36.10M – Welded and seamless wrought steel pipe (pipe schedule dimensions)
  5. The Aluminum Association – Aluminum Electrical Conductor Handbook
FAQ

6063-T6 bus pipe: frequently asked questions

Why is 6063-T6 used for bus pipe instead of pure aluminium?

Pure aluminium conducts better but is too soft to span between insulators without sagging. 6063-T6 keeps about 53 % IACS conductivity while giving a minimum yield of about 172 MPa.

What is the difference between 6063 and 6101 bus pipe?

6101 is a conductor alloy with slightly higher conductivity (about 55 – 59 % IACS depending on temper) and is covered by ASTM B317. 6063-T6 is stronger than the high-conductivity 6101 tempers and is the common choice for outdoor substation bus.

How much current can 4 inch Schedule 40 6063 bus pipe carry?

It depends on the allowed temperature rise, ambient temperature, wind and surface condition. Published ratings for this size are typically in the low thousands of amperes; calculate the rating for your conditions to IEEE 605 or ask the conductor supplier for rated tables.

Is 6063 bus pipe seamless?

Bus pipe for substations is normally seamless extruded pipe to ASTM B241, which gives uniform properties around the circumference. Welded tube is not usually accepted for high-voltage bus.

Does aluminum bus pipe need painting?

No. 6063 resists outdoor corrosion without coating. Contact areas may be plated, and some designers paint the tube to raise emissivity and current rating.

Can you supply metric bus tube?

Yes. Metric outside diameters and walls for IEC-style substations can be supplied; send the OD, wall and length.

Need 6063-T6 bus pipe?

Send the size, schedule, length, quantity and destination. We will reply with availability, certification and a delivered price.